COOLING LOAD REDUCTION OF BUILDINGS USING WATER POND ON ITS ROOF AND SIDE INSULATION

سال انتشار: 1385
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 3,250

فایل این مقاله در 9 صفحه با فرمت PDF قابل دریافت می باشد

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این مقاله:

شناسه ملی سند علمی:

CECB05_159

تاریخ نمایه سازی: 20 دی 1384

چکیده مقاله:

computer program was developed and applied to an enclosure in Shiraz, Iran. The enclosure data were fed into the computer program and calculated hourly inside temperature was compared with experimental taken from this enclosure. Ensuring that the developed software represents the main characteristic of the enclosure, the effect of window orientation and using pond roof and side insulation on reduction of cooling load was examined quantitatively. The cooling load corresponding to the bare enclosure was compared with pond roof and side insulation that has the minimum radiation through the walls. It wasfound that a cooling load reduction of 43.1%, 47.5% and 82.2% may be obtained by using side insulation, pond roof and pond roof with sideinsulation respectively for a good orientation of the window.