Voltage Transformer Protection Based on Distinguishing Ferroresinance from Permanent Faults
سال انتشار: 1394
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 756
فایل این مقاله در 10 صفحه با فرمت PDF قابل دریافت می باشد
- صدور گواهی نمایه سازی
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
COMCONF01_179
تاریخ نمایه سازی: 8 آذر 1394
چکیده مقاله:
Ferroresonance is highly probable in voltage transformers connected to ungrounded power systems.It is important to damp transient oscillations after ferroresonance occurrence in order to improve accuracy of measurements as well as protecting voltage transformer. One of the most effective methods to suppressferroresonance oscillations is connecting a damping resistor at open delta connection in three phase systems. However, when a permanent fault happens, zero sequence currents damage the resistor severely.This paper offered a new algorithm to distinguish ferroresonance conditions from permanent faults andisolate the damping resistor when a permanent fault condition is detected. Simulation results certify the accuracy and practicality of the proposed method.
کلیدواژه ها:
نویسندگان
Mohammad Hadi Zare
Faculty of Electrical and Computer Engineering, Yazd University, Yazd, Iran
Ahmad Mirzaei
Faculty of Electrical and Computer Engineering, Yazd University, Yazd, Iran
مراجع و منابع این مقاله:
لیست زیر مراجع و منابع استفاده شده در این مقاله را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود مقاله لینک شده اند :