Fully Fresh Air Air-conditioning System Equipped with Double Heat Pipe Based Heat Recovery Technology

سال انتشار: 1391
نوع سند: مقاله ژورنالی
زبان: انگلیسی
مشاهده: 854

فایل این مقاله در 8 صفحه با فرمت PDF قابل دریافت می باشد

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این مقاله:

شناسه ملی سند علمی:

JR_IJE-26-1_012

تاریخ نمایه سازی: 17 خرداد 1393

چکیده مقاله:

Using of double heat pipe based heat exchanger (HPHX) in a conventional fully fresh air airconditioning (AC) system was examined in the present study. The fabricated HPHXs were tested underthe actual conditions and the measured data were used to study the performance of the existing ACsystem (System A) and AC system equipped with the double HPHXs (System B) for a yearly operation through modeling in the TRNSYS software. Simulation results showed that the System B with the six and eight-row HPHXs, could maintain the air conditions within the recommendations. However, it was found that the System B with the double eight-row HPHXs is superior in terms of energy savings

کلیدواژه ها:

Heat Pipe Based Heat Exchanger ، Air-conditioning System ، Energy Savings ، TRNSYS Software

نویسندگان

m Ahmadzadehtalatapeh

Department of Marine Engineering, Chabahar Maritime University, ۹۹۷۱۷-۵۶۴۹۹, Chabahar, Iran

y.h yau

Department of Mechanical Engineering, University of Malaya, ۵۰۶۰۳ Kuala Lumpur, Malaysia