Evaluation of Coordinate Compensator Structure Based on Power Injection Model for Loading Margin Enhancement in Power Systems

سال انتشار: 1392
نوع سند: مقاله ژورنالی
زبان: انگلیسی
مشاهده: 527

فایل این مقاله در 19 صفحه با فرمت PDF قابل دریافت می باشد

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این مقاله:

شناسه ملی سند علمی:

JR_IJMEC-3-9_002

تاریخ نمایه سازی: 16 فروردین 1395

چکیده مقاله:

In this paper, the structure of Hybrid Power Flow Controller (HPFC) is proposed in order to improve static voltage stability characteristics. HPFC forms a hybrid controller using IPFC series converters as a hybrid with existing parallel and passive compensator (SVC) in power system. Utilization of hybrid structures makes it possible to use converters for improving performance of both old and existing compensators in power networks. Inthis study, the power injection model (PIM) is used to model the hybrid power flow controller in Newton load flow. The aforementioned model is simulated in MATLAB software. The P-V curves of PQ buses of a typical system are evaluated by a continuous power flow (CPF) method to analyses the effect of this controller on static voltage stability characteristics. Meanwhile, SVC as existing devices in the system and UPFC and IPFC asstate-of-the-art compensator devices are compared with the proposed hybrid structure. The amount of active and reactive power loss and improvement of loading limit of the system are used as main parameters in our comparison.

نویسندگان

Reza Sedaghati

Young Researchers and Elite Club, Beyza Branch, Islamic Azad University, Beyza, Iran