INVESTIGATION OF TRANSIENT OVER VOLTAGE ON STATIC EXCITATION SYSTEM " NEKA "

سال انتشار: 1367
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 2,290

فایل این مقاله در 11 صفحه با فرمت PDF قابل دریافت می باشد

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این مقاله:

شناسه ملی سند علمی:

PSC03_026

تاریخ نمایه سازی: 20 مرداد 1386

چکیده مقاله:

Neka, a turnkey thermal power plant by M/S Brown Boveri CIE CO. consists of 4x440 MW unit with static excitation system and 400 KV sub-station by MI'S Mitsubishi, is located at 50 metres away from power plant. The schematic is as shown in appendix 'G'. It is observed on unit no. 4 whenever 400 kv isolator are manuered at sub-station caused thyrister and its associated fuses failure due to over voltages and over voltages are also observed on other units. This investigation report just briefs salient features of transient over voltage phenomena, sources and remedial measures for present and future similar static excitation system.

نویسندگان

Nanjappa

Generation Technical Dept, TAVANIR Co. Tehran - Iran

مراجع و منابع این مقاله:

لیست زیر مراجع و منابع استفاده شده در این مقاله را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود مقاله لینک شده اند :