Analysis of Furaldehyde Content of the Oil and its Diagnostic Value for Transformer Ageing Fulltext
نويسندهگان:
[ ood ] - N; tional Grid Company Engineering & Technology, Substations & Cables Kelvin Avenue, Leatherhead, Surrey, KT22 7ST United Kingdom [ Pahlavanpour ] - N; tional Grid Company Engineering & Technology, Substations & Cables Kelvin Avenue, Leatherhead, Surrey, KT22 7ST United Kingdom
خلاصه مقاله:
Electrical insulation paper has been aged under controlled conditions. The degradation rates were measured for cotton and Kraft paper in oil at three temperatures, 120-160oC. The furans produced during the ageing process were measured using High Performance Liquid Chromatography. The effect of oxygen and water on the production of furans was investigated. The relationship t Between the furan concentration in tho oil and the change of Degree of Polymerisation of the paper was also examined.
كلمات كليدي:
Furan, Paper, Ageing, Transformer, Oil Aralysis
[ لينک دايمي به اين صفحه: http://www.civilica.com/Paper-PSC14-PSC14_127.html ]
|