A New Single Ended Fault Location algorithm for Combined Transmission Line Considering Fault Clearing Transients without Using Line Parameters

سال انتشار: 1389
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 1,537

فایل این مقاله در 10 صفحه با فرمت PDF قابل دریافت می باشد

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این مقاله:

شناسه ملی سند علمی:

PSC25_007

تاریخ نمایه سازی: 24 بهمن 1390

چکیده مقاله:

This paper presents a new single ended fault location method for underground cable combined with overhead line that uses fault clearing transients instead of fault-generated transients without utilizing line parameters. Applying wavelet transform on voltage samples taken from the sending end of the cable, first, second and third inceptions of traveling waves to the fault locator are detected and faulty section is determined. Then, exact location of fault is calculated. Single-ended algorithm, does not need to the communication system and GPS. Accuracy of algorithm is not affected by aging, climate and temperature variations, which change the wave speed. Fault resistance, fault inception angle and fault distance does not affect accuracy of algorithm. Extensive simulations carried out usingSimPowerSystem toolbox of MATLAB software, confirm the capabilities and high accuracy of the proposed method to find the location of fault under different system and fault conditions.

نویسندگان

Ismail Niazy

Department of Electrical Engineering, Ferdowsi University of Mashhad, Iran

Javad Sadeh

Department of Electrical Engineering, Ferdowsi University of Mashhad, Iran

Ebrahim Niazy

Department of Electrical Engineering, Ferdowsi University of Mashhad, Iran