New Method for On-line Measurement and Evaluation of Partial Discharge in Power Transformers Using Fibre-Optic Transmission
نويسندهگان:
Asghar Akbari - .N. Tousi University of Technology. Dept .Of electrical Engineering Tehran Iran Peter Werle - University of Hannover. Institute of Electric Power system Division of high voltages Engineering Schering- Institute callinstrasse 25 A, D-30167 Hannover Germany Ernst Gockenhach - 2University of Hannover. Institute of Electric Power system Division of high voltages Engineering Schering- Institute callinstrasse 25 A, D-30167 Hannover Germany
خلاصه مقاله:
In this contribution a new technique for on-line and off-line measurement and evaluation of partial discharge is introduced. The difficulties of earlier on-line PD detection are discussed and the advantages of using fibre optic elements for conversion and transmission of PD signals are shown. The investigated modelling methods for transformer coils used for the localisation of PDs are summarised and the required off-line and on-line measurements are explained. Furthermore the experimental results on a power transformer at a substation in Germany are presented.
كلمات كليدي:
Partial Discharge modelling. Power fibre optic
|