CIVILICA We Respect the Science
(ناشر تخصصی کنفرانسهای کشور / شماره مجوز انتشارات از وزارت فرهنگ و ارشاد اسلامی: ۸۹۷۱)

A Study to Estimate Generator Armature Leakage Reactance Using Potier Approximation

عنوان مقاله: A Study to Estimate Generator Armature Leakage Reactance Using Potier Approximation
شناسه ملی مقاله: PSC21_068
منتشر شده در بیست و یکمین کنفرانس بین المللی برق در سال 1385
مشخصات نویسندگان مقاله:

Bank Tavakoli - Amir Kabir University of Technology
Gharagozloo - Tarbiat modares University
Zare Garizi - Iran Grid Management Co.
Mirzaei - Tehran Regional Electric Company

خلاصه مقاله:
Generator armature leakage reactance represents the portion of machine flux that doesn’t link the field and flux path mainly pass the air gaps and often is obtained from manufacturer data. In many old units in an existing power system, however, this parameter is not available. This paper is a study on some Iranian Power plant units for estimating armature leakage reactance from Potier reactance calculation. Two cases was studied, one for units with available leakage reactance to determine the errors and other for units with no leakage available. Study showed this method is capable for estimating leakage reactance with acceptable errors.

کلمات کلیدی:
Leakage reactance, Potier reactance, open-circuit curve, zero-power-factor curve

صفحه اختصاصی مقاله و دریافت فایل کامل: https://civilica.com/doc/19652/