Thermal and Ventilation Performance of a Typical Office in a Hot Humid Climate

عنوان مقاله: Thermal and Ventilation Performance of a Typical Office in a Hot Humid Climate
شناسه ملی مقاله: HVAC05_041
منتشر شده در پنجمین کنفرانس بین المللی گرمایش، سرمایش و تهویه مطبوع در سال 1393
مشخصات نویسندگان مقاله:

Roonak Daghigh - Department of Mechanical Engineering, University of Kurdistan
Nor Mariah Adam - Department of Mechanical and Manufacturing Engineering University Putra Malaysia

خلاصه مقاله:
This paper presents our finding pertaining to thermal comfort parameters, air exchange rate, age of air values and air exchange effectiveness in main office of Mechanical and Manufacturing Engineering Department of University Putra (UPM) Malaysia. It was an air-conditioned office. The tracer gas decay method has been applied during the experimental procedures employed to determine air exchange rate, age of air and, air exchange effectiveness simultaneously, thermal comfort variables were measured. It was found that the office was slightly cool based on ISO 7730, but result of survey revealed that staff found condition to be slightly cool to cool. The results of ventilation study indicate air flow patterns in the occupied zones which approximate perfect mixing . The local air change effectiveness at location for office was found to be 1.01 and the measured air exchange rate is also indicating that the provision of outside air for ventilation is adequate.

کلمات کلیدی:
Experiment, Survey, Tracer decay technique, age of air, Thermal Comfort