A New Scheme for Detection and Compensation of Current- Transformer Saturation

سال انتشار: 1396
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 419

فایل این مقاله در 8 صفحه با فرمت PDF قابل دریافت می باشد

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این مقاله:

شناسه ملی سند علمی:

ICELE02_167

تاریخ نمایه سازی: 7 اسفند 1396

چکیده مقاله:

Current-transformer (CT) is prone to the saturation during the power system faults. The CT saturation may result in malfunction of the protection relays. Nowadays the accurate detection and compensation of the saturation with the use of digital-signal-processing techniques is requested increasingly. This paper presents a new scheme for CT saturation detection and compensation. The first part of the proposed algorithm uses the derivatives of the secondary current signals to estimate the start and the end point of the CT saturation. In the second part, a compensation method based on the modified discrete Fourier transform is proposed to reconstruct the saturated samples. In order to suprress the probable noise and harmonics, a low pass Butterworth filter is used. The performance of the proposed method is evaluated by considering different values of remanent flux, fault type, fault inception angle, decaying DC component of fault current and noise. The obtained results show the effectiveness of the proposed scheme in different conditions

نویسندگان

Seyed Hamid Abbasnia

Department of electrical engineering, Lahijan Branch, Islamic Azad University, Lahijan, Iran

Hossein Mahdinia

Department of electrical engineering, Lahijan Branch, Islamic Azad University, Lahijan, Iran