Thermodynamic analysis of an improved two-stage multi-intercooling transcritical CO2 refrigeration cycle

سال انتشار: 1398
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 282

نسخه کامل این مقاله ارائه نشده است و در دسترس نمی باشد

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این مقاله:

شناسه ملی سند علمی:

ISME24_727

تاریخ نمایه سازی: 21 مهر 1398

چکیده مقاله:

Performance of a two-stage multi-intercooling transcritical CO2 refrigeration cycle containing internal heat exchanger, two intercoolers, ejector and separator, has been analyzed after modification. In the present study, an internal heat exchanger has been included within this cycle for possible improvement in its cooling performance. The impacts of operational parameters such as gas cooler and evaporator temperatures and pressure of gas cooler, on cycle performance have been investigated. Computed results showed that modified cycle improved the maximum coefficient of performance, COP max, by 20.58% compared to the internal heat exchanger two-stage TRCC cycle and 23.2% compared to multi-intercooling two-stage TRCC cycle with ejector expansion device.

نویسندگان

a.r rahmati

Assistant Professor, Department of Mechanical Engineering, University of Khashan,

a gheibi

PhD student, Department of Mechanical Engineering, University of Khashan,