New Method for Inrush Current Mitigation Using Series Voltage-Source PWM Converter for Three Phase Transformer

سال انتشار: 1389
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 1,365

فایل این مقاله در 6 صفحه با فرمت PDF قابل دریافت می باشد

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این مقاله:

شناسه ملی سند علمی:

PEDSTC02_080

تاریخ نمایه سازی: 21 تیر 1391

چکیده مقاله:

Transformer inrush currents have always been a concern in a power industry. Inrush currents generated by unloaded power transformer often reduce power quality on the system. Over the last decades, methods have been proposed to remove transformer inrush currents. To improve this situation, this paper proposes an active inrush current compensator that is capable of reducing the inrush current effectively during start up mode. The method uses a voltage source PWM converter is connected in series to the transformer that produce a dynamic resistor in series with transformer and remove inrush current. This method was tested by PSCAD/EMTDC simulation. Simulate shows that proposed method removes inrush current completely. This strategy is easier to implement because it has simple control method and requires no information of the transformer parameters, power on angle circuit breaker and measurement of residual flux and so on.

نویسندگان

abbas ketabi

Department of Electrical Engineering University of Kashan Kashan, Iran

alireza hadidi zavareh

Department of Electrical Engineering University of Kashan Kashan, Iran