How to deal with gassing transformers

سال انتشار: 1380
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 1,811

فایل این مقاله در 11 صفحه با فرمت PDF قابل دریافت می باشد

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این مقاله:

شناسه ملی سند علمی:

PSC16_111

تاریخ نمایه سازی: 3 مهر 1386

چکیده مقاله:

Power transformers are generally reliable constituents of a transmission or distribution network. However, the cost of a transformer failure can be very high, not just the price of a new transformer but also the costs incurred by a forced outage and loss of security to the system. It is certainly, therefore, in the asset owner’s interest to take an informed interest in their condition. Condition assessment and monitoring techniques have received a technological boost in the last few years but at the heart of it is a technique dating back several decades. Dissolved gas analysis (DGA) is still the best technique for detecting abnormalities in transformers. The sampling of oil and subsequent analysis for dissolved gases is well defined in IEC60567 (1). The interpretation of the results is less straightforward; there are recognised standards (2,3) and other publications (4,5). Whilst they

کلیدواژه ها:

Transformers ، Dissolved gas analysis. Furfural analysis ، radio frequency interference ، condition monitoring

نویسندگان

Pahlavanpour

National Grid Company plc Network Engineering, Kelvin Avenue, Leatherhead Surrey, KT۲۲ ۷ST, UK

Lapworth

National Grid Company plc Network Engineering, Kelvin Avenue, Leatherhead Surrey, KT۲۲ ۷ST, UK

Wilson

National Grid Company plc Network Engineering, Kelvin Avenue, Leatherhead Surrey, KT۲۲ ۷ST, UK

مراجع و منابع این مقاله:

لیست زیر مراجع و منابع استفاده شده در این مقاله را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود مقاله لینک شده اند :
  • IEC60567, :Guide for the sampling of gases and of oil ...
  • IEC60599, 'Mineral oi I-impregnated equipment in service- interpretation of dissolved ...
  • IEEE :Guide for the interpretation of gases generated in oil- ...
  • guidelines for New؟ [4] Mollmann, A. and Pah lavanpour, B., ...
  • Pah lavanpour, B. and Lapworth, J., 'Recent advances in the ...
  • Lech, W. and Tyminski, L., 'Detecting transformer winding damage by ...
  • Vaessen, P.T.M. and Hanique, E., 'A new frequency response analysis ...
  • Dick, E.P. and Erven, C.C, 'Transformer diagnostic testing by frequency ...
  • Lapworth, J. A. and McGrail, A.J., :Transformer Winding Movement Detection ...
  • IEC61198, Mineral insulating oils, methods for the determi nation of ...
  • De Pablo, A and Pah lavanpour, B., 'Furanic compound analysis: ...
  • Heywood, R. and Pah lavanpour, B. 'Analysis of Furaldehyde COntent ...
  • BURTON.J., GRAHAM J, HALL A.C., LAVER J.A., and OLIVER A.J., ...
  • BURTON P.J., CARBALLEI RA M., DUVAL M., FULLER J., GRAHAM ...
  • GRIFFIN P.J., LEWAND L. R. and PAH LAVANPOUR B., Paper ...
  • PAHLAVAN POUR B., HEYWOOD R., and WILSON G., Power transformer ...
  • SCHEIR J., CAMINO G., AVIDANO M. and TUMIATTI W., Study ...
  • degradation of cellulosic insulating paper, J. Appl. Polym. Sci., Vol. ...
  • DE PABLO A., Furfural and ageing: How are they related, ...
  • McGrail, A. and Lapworth, J. 'Experience with transformer _ monitoring ...
  • Oommen, T.V., Ronnau, R.A. and Girgis, R.S., 'New mechanism of ...
  • نمایش کامل مراجع