چکیده مقاله:
Installing the renewable energy sources (RESs) in distribution networks changes the fault current direction, increases the fault current level and, consequently, eliminates the protection coordination between the protective devices. Overcurrent relays are among the most important protective devices in distribution networks. Proper performance of the protective system requires protection coordination between the overcurrent relays. The present paper proposes a new protection coordination scheme using digital directional overcurrent relays (DOCRs) and dual-setting digital overcurrent relays (DS-DOCRs) in the distribution network in the presence of the RESs and energy storage systems (ESSs). For this purpose, a multi-stage objective function was used. In the first stage, a weighted objective function was employed to optimize the size and location of the RESs as well as the location and impedance of the FCLs in order to reduce the loss, improve the voltage profile and decrease the variation of the feeders' currents at the connection time of the RESs. In the second stage, DOCR and DS-DOCR settings optimization, which included parameters A and B in addition to parameters I{}_{p} and TDS, was used to restore the lost protection coordination for the fault current in the shortest possible time. The simulation results on the IEEE ۳۳-bus network in the presence of RESs using genetic algorithm and PSO algorithm method as well as DPL programming language in DIgSILENT software showed that the total operating time of digital relays and network loss were reduced and voltage profile was significantly improved.
کلیدواژه ها:
Dual-setting digital directional overcurrent relays ، Distribution network ، Power losses ، Voltage profile ، Fault current limiter (FCL) ، Protection Coordination
نویسندگان
M. Faghihi Rezaei
Department of Electrical Engineering, Saveh Branch, Islamic Azad University, Saveh, Iran.
M. Gandomkar
Department of Electrical Engineering, Saveh Branch, Islamic Azad University, Saveh, Iran.
J. Nikoukar
Department of Electrical Engineering, Saveh Branch, Islamic Azad University, Saveh, Iran.
مراجع و منابع این مقاله:
لیست زیر مراجع و منابع استفاده شده در این مقاله را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود مقاله لینک شده اند :