Detection and localization of internal turn-to-turn short circuits in transformer windings by means of negative sequence analysis

سال انتشار: 1393
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 942

فایل این مقاله در 7 صفحه با فرمت PDF قابل دریافت می باشد

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این مقاله:

شناسه ملی سند علمی:

PSC29_303

تاریخ نمایه سازی: 6 آذر 1393

چکیده مقاله:

Internal turn-to-turn short circuits are the most difficult types of faults to detect within the transformers. This paper proposes a new, simple and efficient algorithm in order to protect transformers against these faults. Using this protection algorithm which is based on negative sequence analysis, make it possible to detect and also locate low level inter-turn short circuits which typically cannot be detected by the traditional differential algorithm before they extended into more severe faults. Furthermore, the proposed algorithm is stable in the case of external faults as well as load imbalance condition. In this work, first, a typical transformer is modeled based on Finite Element Method to simulate the transformer behavior under different operation conditions. Then, the accuracy and performance of new protection technique in detection and localization of inter-turn faults is studied by applying it to the simulated transformer.

نویسندگان

Malihe Abi

Faculty of Electrical and Computer Engineering BabolNoshirvani University of Technology Babol, Iran

Mohammad Mirzaie

Faculty of Electrical and Computer Engineering BabolNoshirvani University of Technology Babol, Iran